| Recommendations for the determination of capillary tube size |
 |
Table considers condensing temperature Tc = 45 °C and heat exchanger in capillary..
Increase length 2% per each K of increase of condensing temperature..
|
 |
| TABLE FOR REFRIGERANT R22 (LBP) |
| Capillary tube length (m) |
| QASH |
M |
Capillary tube internal diameter (mm) & Evaporating temperature (°C) |
| 0,6 | 0,7 | 0,8 | 0,9 | 1 | 1,2 | 1,5 |
| kcal/h | kg/h | -30 | -23,3 | -30 | -23,3 | -30 | -23,3 | -30 | -23,3 | -30 | -23,3 | -30 | -23,3 | -30 | -23,3 |
| 100 | 2,16 | 2,63 | 2,76 | | | | | | | | | | | | |
| 120 | 2,59 | 1,81 | 1,90 | | | | | | | | | | | | |
| 130 | 2,80 | 1,54 | 1,62 | | | | | | | | | | | | |
| 140 | 3,02 | 1,33 | 1,39 | 3,06 | 3,20 | | | | | | | | | | |
| 150 | 3,23 | 1,15 | 1,21 | 2,66 | 2,79 | | | | | | | | | | |
| 160 | 3,45 | 1,01 | 1,06 | 2,33 | 2,45 | | | | | | | | | | |
| 170 | 3,66 | | | 2,07 | 2,17 | | | | | | | | | | |
| 180 | 3,88 | | | 1,84 | 1,93 | | | | | | | | | | |
| 190 | 4,10 | | | 1,65 | 1,73 | 3,42 | 3,58 | | | | | | | | |
| 200 | 4,31 | | | 1,49 | 1,56 | 3,08 | 3,23 | | | | | | | | |
| 215 | 4,64 | | | 1,29 | 1,35 | 2,65 | 2,78 | | | | | | | | |
| 230 | 4,96 | | | 1,12 | 1,18 | 2,31 | 2,42 | | | | | | | | |
| 245 | 5,28 | | | 0,99 | 1,04 | 2,03 | 2,13 | | | | | | | | |
| 260 | 5,61 | | | | | 1,80 | 1,89 | 3,42 | 3,59 | | | | | | |
| 275 | 5,93 | | | | | 1,60 | 1,68 | 3,05 | 3,20 | | | | | | |
| 300 | 6,47 | | | | | 1,34 | 1,41 | 2,55 | 2,68 | | | | | | |
| 320 | 6,90 | | | | | 1,17 | 1,23 | 2,23 | 2,35 | | | | | | |
| 340 | 7,33 | | | | | 1,04 | 1,09 | 1,97 | 2,07 | 3,53 | 3,70 | | | | |
| 360 | 7,76 | | | | | | | 1,75 | 1,84 | 3,13 | 3,29 | | | | |
| 380 | 8,19 | | | | | | | 1,57 | 1,65 | 2,80 | 2,94 | | | | |
| 400 | 8,62 | | | | | | | 1,41 | 1,48 | 2,52 | 2,64 | | | | |
| 450 | 9,70 | | | | | | | 1,11 | 1,17 | 1,97 | 2,07 | | | | |
| 500 | 10,78 | | | | | | | | | 1,58 | 1,66 | | | | |
| 550 | 11,86 | | | | | | | | | 1,30 | 1,36 | 3,56 | 3,74 | | |
| 600 | 12,94 | | | | | | | | | 1,08 | 1,14 | 2,96 | 3,11 | | |
| 650 | 14,01 | | | | | | | | | 0,92 | 0,96 | 2,50 | 2,63 | | |
| 700 | 15,09 | | | | | | | | | | | 2,14 | 2,25 | | |
| 750 | 16,17 | | | | | | | | | | | 1,85 | 1,95 | | |
| 800 | 17,25 | | | | | | | | | | | 1,62 | 1,70 | | |
| 850 | 18,32 | | | | | | | | | | | 1,42 | 1,50 | | |
| 900 | 19,40 | | | | | | | | | | | 1,26 | 1,33 | | |
| 950 | 20,48 | | | | | | | | | | | 1,13 | 1,18 | | |
| 1000 | 21,56 | | | | | | | | | | | 1,01 | 1,06 | 3,58 | 3,68 |
| 1100 | 23,71 | | | | | | | | | | | | | 2,97 | 3,01 |
| 1200 | 25,87 | | | | | | | | | | | | | 2,51 | 2,50 |
| 1300 | 28,03 | | | | | | | | | | | | | 2,14 | 2,11 |
| 1400 | 30,18 | | | | | | | | | | | | | 1,85 | 1,80 |
| 1500 | 32,34 | | | | | | | | | | | | | 1,62 | 1,56 |
| 1600 | 34,49 | | | | | | | | | | | | | 1,43 | 1,36 |
|
 |
QASH is the cooling capacity under ASHRAE (LBP) condition corresponding to the indicated mass flow rate M (liquid subcooled down to 32 °C, return gas superheated up to 32 °C)..
The relationship between length and diameter is, approximately: (L / L0) = (D / D0)5,4..
NOTE: R22 is not recommended for LBP use..
|
|
| |
| |
|
|